SSD 690+ AC Frequency Inverter for 45kW (60HP) 400V 3 Ph motor to 87A at high overload or 55kW (75HP) to 105A when Fan/Pump rated. Operates in VxF, Sensorless Flux Vector or Full Closed Loop Flux Vector control (when the optional encoder board is fitted). Simple set-up and ready to run in VxF from its default settings.
Dimensions: Size E 257mm Wide x 312mm Deep x 676mm High overall.
Overload: 150% x 60 seconds and 180% for 0.5seconds.
Speed Control Range: 0/120Hz (default), 0/240Hz or 0/480Hz.
Braking: 100% x 20 seconds duty or 30% continuous into minimum 12 Ohm external resistor. See the Resistor options linked below or use the 'Which Resistor' button on this page.
Features: 4 x Analogue Inputs, 8 Digital Inputs, 3 Analogue outputs, 3 Digital outputs (relay contacts).
Input Current: 95A at high overload or 110A when Fan/Pump rating set.
Input Voltage: 380/460V three phase +-10% at 50/60Hz.
Input fuse: 100A at high overload and 125A when Fan/Pump rating set, to suit input bridge at 18000A²s.
Mounting: Wall mount in clean environment or cubicle mount via M6 screw fixings on 150mm x 630mm centres.
Ambient: Rated at 40C.
Ventilation space above and below: 70mm.
Ventilation space at sides: 0mm.
Heat Loss: 880W at max output for high overload or 1242W when Fan/Pump rating set.
Part Number: 690-432870E0-B00P00-A400. Legacy Part Number was: 690PE/0450/400/0011/UK/0/0/0/0/B0/0/0. Exactly the same as SSD Drives and Eurotherm Drives branded product bearing the same Legacy Part Number.
The menu uses simple to understand English-language terms to describe its selection and functions. The default is English, but can be changed to German, French, Spanish, Italian, Polish, Swedish and Portuguese, by going to 'System', then 'Languages' and selecting the language required.
The 690P Technical Product Manual and Software Manuals can be downloaded from the link below...