SSD 690P AC Frequency Inverter for 180kW (250HP) 400V 3 Ph motor to 361A at high overload (Heavy Duty) or 220kW (300HP) to 420A when normal duty (Fan/Pump rated), operates in VxF, Sensorless Flux Vector or Full Closed Loop Flux Vector control (when the optional encoder board is fitted).
Simple set-up and ready to run in VxF from its default settings.
Requires external choke - part number CO389936U402 (not included)
Size G - 455mm Wide x 465mm Deep x 1384mm High (includes length of exhaust duct). Space is required at sides for bars and above for roof mounting fan.
Weight - 100kg
Overload - 150% x 60 seconds and 180% for 0.5seconds at high overload rating or 110% for 10 seconds for normal duty (fan/pump rating).
Switching frequency - 2.5kHz at full output, reducing to 1.2kHz at maximum overload.
Speed Control Range - 0/250Hz at continuous rating, or 120Hz if used to maximum overload.
Braking - none.
4 x Analogue Inputs, 8 Digital Inputs, 3 Analogue outputs, 3 Digital outputs (relay contacts).
Input Current - 336A at high overload or 402A when Fan/Pump rating set.
Input Voltage - 380/460V three phase +-10% at 50/60Hz.
Input fuse - 400A at high overload or 450A when Fan/Pump rating set - to suit input bridge at 813000A²s
Cubicle mounting.
Rated at 40C Ambient.
Ventilation fan requires a separate 115V supply fused at XA.
Heat Loss at max output - 3723W at high overload and 4409W when Fan/Pump rating set.
Manufacturer Part Number is 690-433361G1-000P00-A400. Legacy Part Number was 690PG-1800-400-0011-UK-0-0-0-0-00-115-0. Exactly the same as SSD Drives and Eurotherm Drives product bearing the same Legacy Part Number.
The menu uses simple to understand English-language terms to describe its selection and functions. The default is English, but can be changed to German, French, Spanish, Italian, Polish, Swedish and Portuguese, by going to 'System', then 'Languages' and selecting the language required.
Download the 690P Technical and Software Manual from the links below:-