SSD 690+ AC Frequency Inverter for 15kW (20HP) to 31A at high overload or 18.5kW (25HP) to 38A 400V 3 Ph motor when Fan/Pump rated, operates in VxF, Sensorless Flux Vector or Full Closed Loop Flux Vector control (when a 15V encoder is connected to the 'Slave' terminals of the System board).
Size C - 201mm Wide x 208mm Deep x 348mm High.
Overload - 150% x 60 seconds and 180% for 0.5seconds.
Speed Control Range - 0/120Hz (default), 0/240Hz or 0/480Hz.
Braking - 100% x 20 seconds or 25% continuous into minimum 50 Ohm external resistor. See the Resistor options linked below or use the 'Which Resistor' button on this page.
4 x Analogue Inputs (one high speed at +-12 Bit resolution), 8 Digital Inputs, 3 Analogue outputs, 3 Digital outputs (relay contacts), 5 x Programmable Digital Inputs/Outputs, 2 x Encoder inputs (15V full quadrature with complements) and repeat buffered encoder output.
Input Current - 37A at high overload or 44A when Fan/Pump rating set.
Input Voltage - 380/460V three phase +-10% at 50/60Hz.
Input fuse - 40A at high overload or 50A when Fan/Pump rating set - to suit input bridge at 6000A²s
Wall mount in clean environment or cubicle mount.
Rated at 40C Ambient.
Ventilation space above and below - 70mm.
Ventilation space at sides - 15mm.
Heat Loss at max output - 500W at high overload or 610W when Fan/Pump rating set.
Mounting - M6 screw fixings on 150mm x 335mm centres.
Full part number is - 690-432300C0-B0SP00-A400 - was 690PC-0150-400-0011-UK-0-0-0-SHTTL-B0-0-0 - Exactly the same as SSD Drives and Eurotherm Drives - 690PC-0150-400-0010-UK-0-0-0-SHTTL-B0-0-0.
The menu uses simple to understand English-language terms to describe its selection and functions. The default is English, but can be changed to German, French, Spanish, Italian, Polish, Swedish and Portuguese, by going to 'System', then 'Languages' and selecting the language required.
Replaces:- 620STD/0150/400/0010/UK/ENW/0000/000/B0/000/000, 620COM/0150/400/0010/UK/ENW/0000/000/B0/000/000, 620ADV/0150/400/0010/UK/ENW/0000/000/B0/000/000,